Examples of modernisation cooling tower SK-400 on objects of the industry:

Cooling tower SK-400 on OAO «VORONEZHSINTEZKAUCHUK» Voronezh city.

  • Productivity on water Q = 3200 m ³/hour.
  • Inlet water temperature Т1 = 35 °С
  • Outlet water temperature Т2 = 22 °С
  • Difference of temperatures ∆t = 13 °C
  • Air Temperature +35÷37 °C
  • Thermal capacity W = 48,38 Gkal/hour.
  • Capacity of fan N = 200 кВт.
  • The irrigation Area = 384 м²

The water distributive system with modernised bell-shaped atomizers SVR-25М provides a uniform irrigation on all area of an irrigation. Productivity of the fan = 2 880 000 m /hour Regulation of speed of turns.


Cooling tower SK-400 on OAO «Sibur-Himprom» Perm city

  • Productivity on water Q = 3200 m ³/hour.
  • Inlet water Temperature Т1 = 35 °С
  • Outlet water Temperature Т2 = 22 °С
  • Difference of temperatures ∆t = 13 °C
  • Air temperature +35÷37 °C
  • Thermal capacity W = 41,6 Gkal/hour.
  • Capacity of fan N = 200 кВт.
  • Productivity of the fan = 2 880 000 m ³/hour.
  • Regulation of speed of turns.
  • The irrigation area = 384 м²

It is established WDS with self-cleared pipes of the variable section, allowing to cool water with pollution to 1000 mg/litre, equipped with modernised bell-shaped atomizers SVP-25М which provide a uniform irrigation.


Cooling tower SK-400 OAO «Toljattikauchuk» Tolyatti city

  • Productivity on water Q = 3000 m ³/hour.
  • Inlet water temperature Т1 = 35 °С
  • Outlet water temperature Т2 = 25 °С
  • Difference of temperatures ∆t = 10 °C
  • Thermal capacity W = 3000х10х1,163 = 33,89 Mwt.
  • Capacity of fan N = 200 Kw.

After modernisation of cooling tower SK-400, on power saving up technology, at the expense of a uniform irrigation of water and efficiency of ventilation of air, difference of temperatures, and as consequence has increased, thermal capacity has increased, and the current consumption has considerably decreased. At the project adjustment, necessary thermal capacity has been provided at 60 % to fan loading.