A block type BMG-210M micro-cooling tower of the new generation consists of the modular metal carcass. It has sheeting, a water-distribution system, a plastic drain pan, and highly effective polymeric sprinklers and drift eliminators. Slow-go, two- speed motor fan with a noise absorbing body and with improved aerodynamics. The ventilating fan is equipped with high-profile polished blades made of the multilayer fiberglass, manufactured per aviation technology. It is a low noise fan. The air is supplied by the ventilating fan in a mode of regulating of turns that allows minimizing electric energy consumption. The electric motor is three-phase, slow-go, sizing is selected as per the calculations of power required, it has a full protection from corrosion and moisture penetration inside the motor, it is cooled by the outdoor air, windings and bearings have protection against high temperature, vibration monitoring is provided as well. A special mode for windings heating and drying is foreseen to preserve insulation in safe condition at lengthy downtime.

Parameters Unit of measurement Area of irrigation
Range of hydraulic loads m³/hr 80-300
Design hydraulic load m³/hr Individual calculations on the bases of initial data furnished by the Client
Thermal load, min. МCal/hr per calculations
Temperature zone of cooling оС per calculations
Inlet water temperature, max. оС 65
Drift elimination, max % 0.02
Inlet water pressure, min m water column 7
Inlet pipeline diameter mm calculated as per hydraulic load
Outlet pipeline diameter at the exit from basin mm calculated as per hydraulic load
Quantity of nozzles pieces per calculations
Catch water tank active capacity liters 500
Catch water baffle boards capacity liters 700
Number of ventilating fans pieces. 1
Diameter of the ventilating fan мм 2370
Number of blades шт. 3÷6
Electric motor design power KW 11÷22
Electric motor design power V/Hz 380/50
Electric equipment class of protection, not below   IP55
Noise level at a distance of 10 m, max. db 70
Overall dimensions (LxWxH) mm 3860х4190х6300
Working mass kgs 5730
Soft start device, 2-speed operating mode, control, insulation drying pieces -
Frequency transducer (temperature control, anti-icing system) pieces 1
Reversing device (anti-icing) pieces -
Replacement of СК-400 cooling tower for BMG-210М (ОАО Acrylat, City of Dzerzhinsk )
Replacement of СК-400 cooling tower for BMG-210М (ОАО Acrylat, City of Dzerzhinsk ) of 3500 m³/hr capacity, on the site of D = 22m2 (installation was done on the same place on top of the old basin without its capital repairs, cost of revamping 2÷3 million rubles, power consumption goes down from 250 KW to 110 KW).
In this particular case the design solution excluded: expensive concrete basins typical for standard cooling towers, the cooling towers proper, pumping house with in ground machine room and concrete inlet chambers with obsolete pumps.
Автоматическое регулирование температуры воды, электронная система антиобледенения, полный мониторинг.
Examples of BMG-210М cooling towers use in closed-circuit water systems.

City of Revda, Nizhneserginsk ММZ. Water block capacity on the bases of BMG-210М mounted on the roof is W = 57Мegawatts. Floor space F=140m2 Q=2450m3/hr.


ОАО Magnezit, City of Satka, Chelyabinsk oblast.

The 4-section BMG-210 М1 cooling tower (F = 44 m2) in place of the 4-sections F=64m2 (F=256m2) after its revamping in line with the new technology.

The following readings have been taken at the 35°C heat:
  • Hot water temperature Т1 = 44,5 °С
  • Cooled water temperature Т2 = 24,1 °С
  • t=20,4 °С
  • Air temperature +35?37 °С
  • Hydraulic load 720 m³/hr
  • Thermal power W = 720х20.4х1.163= 17 МW

ОАО NOVATOP, Plywood factory, City of Velikiy Ustyug
  • Water capacity Q = 600 m³/hr.
  • Hot water temperature Т1 = 32 °С
  • Cooled water temperature Т2 = 26 °С
  • Air temperature +18 °С
  • Temperature differential ∆t = 6 °C
  • Thermal power W = 3,6 GCal/hr.
  • Fan capacity N = 15х2 = 30 KW.

ОАО Zapadno-Sibirskiy metallurgicheskiy combinat, (Still mill), City of Novokuznetsk

BMG-210М cooling towers - 3 off.

  • Water capacity Q = 800 m³/hr.
  • Hot water temperature Т1 = 43 °С
  • Cooled water temperature Т2 = 30 °С
  • Temperature differential ∆t = 13 °C
  • Fan capacity N = 11 KW.
  • Thermal power W = 10,4 GCal/hr.

Rostokinskiy works of concrete components, ОАО DCK-1 (Integrated house-building factory-1)
  • Moscow City
  • Water capacity Q = 200 m3/hr.
  • Hot water temperature Т1 = 45 °С
  • Cooled water temperature Т2 = 25 °С
  • Temperature differential ∆t = 20 °C

ОАО SeverSteelAvto, City of Yelabuga, January 15, 2008.

Installed and ready for operation are 3 BMG-210М1 cooling towers with 4-blades fans BG-24-4. Start-up is scheduled for May 2008.

  • Water capacity Q = 1000 m3/hr.
  • Hot water temperature T1= 35 °С
  • Cooled water temperature T2 = 29 °C
  • Temperature differential ∆t = 6 °С
  • Thermal power W = 1000х6х1,163= 6,97МWatt.
  • BG-24-4 fan capacity, N = 15 KW.